Ecomax 'LC'
Entrée TOR
-J5.ID1: C1 – Comp. –Panne
-J5.ID2: C1 – HP
-J5.ID3: C1 – Ventil. –Panne
-J5.ID4: C2 – Comp. –Panne
-J5.ID5: C2 – HP
-J5.ID6: C2 – Ventil. –Panne
-J5.ID7: ON/OFF / M/A à distance
-J5.ID8: Reset / Contrôle à distance
-J7.ID9: Eau – Débit
-J7.ID10:
-J7.ID11:
-J7.ID12:
-J8.ID13:
-J8.ID14:
CLIMATIC 50 - Manuel d'utilisation – Gammes Chillers
Sortie TOR
-J12.NO1: C1 – (Vis) Reset Comp.
-J12.NO1: C1 – (Piston) Vanne 1 Comp., 1
-J12.NO1: C1 – (P322) Vanne 2 Comp., 1
-J12.NO2: C1 – (Vis) Vanne 50%
-J12.NO2: C1 – (Piston) Comp 2
-J12.NO3: C1 – (Vis) Vanne 75%
-J12.NO3: C1 – (Piston) Vanne 1 Comp., 2
-J12.NO3: C1 – (322P) Vanne 1 Comp., 1
-J13.NO4: C2 – (Vis) Reset Comp.
-J13.NO4: C2 – (Piston) Vanne 1 Comp., 1
-J13.NO4: C2 – (322P) Vanne 2 Comp., 1
-J13.NO5: C2 – (Vis) Vanne 50%
-J13.NO5: C2 – (Piston) Comp.2
-J13.NO6: C2 – (Vis) Vanne 75% .
-J13.NO6: C2 – (Piston) Vanne 1 Comp., 2
-J13.NO6: C2 – (322P) Vanne 2 Comp., 1
-J14.NO7: C1 - (Vis) Comp.
-J14.NO7: C1 - (Piston) Comp., 1
-J15.NO8: C1 – Ventilation 1
-J15.NO8: C1 – Ventilation 1 –Haute Vitesse
-J15.NC8: C1 – Ventilation 1–Basse Vitesse
-J16.NO9: C1 – Vanne liquide
-J16.NO10: C2 – Vanne liquide
-J16.NO11: C2 – (Vis) Comp.
-J16.NO11: C2 – (Piston) Comp. 2
-J17.NO12: C2 – Ventilation 1
-J17.NO12: C2 – Ventilation1–Haute Vitesse
-J17.NC12: C2 –Ventilation1–Basse Vitesse
-J18.NO13: Alarme générale
BM50 – Carte de base
Entrée Analogique
-J2.B1: C1 – HP (4~20ma -1~29b)
-J2.B2: C1 – BP (4~20ma -1~6b) *
-J2.B3: C2 – HP (4~20ma -1~29b)
-J2.B4: C2 – BP (4~20ma -1~6b) *
-J3.B5: Eau – Sortie (NTC)
-J3.B6: Eau – Entrée (NTC)
-J6.B7: LCW Eau T cond Sortie
-J6.B8: Air Extérieur (NTC)
* Si pas de détendeur Electronique
CL50-CHILLERS/IOM/1105-F
Sortie Analogique
-J4.Y1: C1 – Ventilation 2, 3, 4, 5
-J4.Y1: C1 – Ventilation 1, 2, 3, 4 si 2 vitesses
-J4.Y2: C2 – Ventilation 2, 3, 4, 5
-J4.Y2: C2 – Ventilation 1, 2, 3, 4 si 2vitesses
-J4.Y3: C1 – Ventilation 1 – PWM
-J4.Y4: C2- Ventilation 1 – PWM
40
40