Operation
7.3 Incremental heating test
Proceed as follows during the incremental
heating test:
1. Fully open the valve and operate the hand-
wheel (see 3.4 on page 28).
Control the flow temperature using
the heat generator control.
2. Heat up to a flow temperature between
20 °C and 25 °C for a minimum of 3 days.
3. Then heat at maximum design temperature
for a minimum of 4 days.
7.4 Positioning the cover plate
1. After having completed all building work,
remove the "Unibox E RTL" protection
cover.
2. Position the cover plate on "Unibox E RTL".
Illustr. 9: Positioning the cover plate
8.
Operation
Adjust the medium temperature of the surface
temperature balance circuit using the hand-
wheel (see 3.4 on page 28).