the stove. Horizontal connection pieces of over 0.5 m must rise towards the chimney at an
angle of 10 degrees. Any pipes which are not heat insulated or verti-
cal must not be longer than 1 metre.
The requirements of the Fire Regulations (FeuVO) apply, as well as
local building regulations such as for the chimney standards DIN
4705, EN 13384, DIN 18160 and EN 15287.
Connection pieces must be tested to DIN EN 1856-2. Measurement
X (distance from flammable construction and other materials) must
be as defined by the manufacturer of the connection piece.
Fitting to a chimney with a functional height of less than 4 m, or
if several stoves are being fitted, less than 5 m, is not permitted.
(See: Data for chimney calculations / Chapter 4.) A maximum of
two other fires can be connected to the chimney to be connected to the stove.
For safety reasons it is not permitted to use a steam extractor hood to remove air
when the stove is producing heat.
1.9
Choice of flue gas connection placement
The flue outlet is attached to the back of the stove as standard. If a connection to the side
or the top is required, then the unused connection must be closed off.
1.9.1
Top connection (Fig. 1)
•
Remove the rear flue outlet (1) by loosening the screws.
•
Close off flue gas connection behind stove from outside using the blank cover supplied
(12) and screw this tight
•
Rear masking cover (8) should be swung upwards and closed
•
Remove flue gas cover (3) and the large hob plate (2)
•
Connect the flue connector (1) from below to the opening of the flue gas cover (3) of
the large hob plate (2) and screw tight
•
Replace the hob plate (2)
1.9.2
Side connection (Fig. 1)
•
Remove the rear flue outlet (1) by loosening the screws.
•
Remove the side cover plate (10) by loosening the screws
•
Loosen the screws in the side blank cover (12) and remove cover
•
Fasten flue outlet (1) to the side panel and screw tight
•
Close off flue gas connection behind stove from outside using the blank cover supplied
(12) and screw this tight
•
Rear masking cover (8) should be swung upwards and closed
PLEASE NOTE:
37
X